Search
Close this search box.

WE HANDLE INQUIRIES THROUGH EMAIL MORE EFFICIENTLY

WE HANDLE INQUIRIES THROUGH EMAIL MORE EFFICIENTLY

PILZ Pilz PNOZ m1p base unit

Pilz PNOZ m1p base unit

PILZ

We are PILZ Product supplier in India

Article No. 773100

Configurable safe small controllers PNOZmulti Classic, base unit, expandable, serial interface RS232, 20 safe digital inputs, 4 safe semiconductor outputs, 2 safe relay outputs.

Electrical data

Purpose of U1System supply  
Supply voltage (V)24  V
Type of supply voltage U1DC  
Purpose of U2Supply of SC outputs  
Supply voltage 2 (V)24  V
Type of supply voltage U2DC  
Tolerance of U2 
Potential isolation U2Yes  

Inputs

Number of digital inputs20  
Signal level at input at 0-3 – +5 VDC  
Potential isolation inputNo  

Semiconductor outputs

Number of semicond. outputs4  
Potential isolation of S/C OYes  
S/C output short circuit proofYes  

Semiconductor outputs (standard)

Number of auxiliary outputs1  
Galv. isol. n/safe SC OYes  
Short circ. prot. n/safe S/C OYes  
Signal level at 1 n/safe S/C OUB – 0.5 VDC at 0.5 A  

Test clock outputs

Number of test pulse outputs4  

Relay outputs

Number of relay outputs2  
Utilisation cat. AC/DC1 stand.EN 60947-4-1  
Voltage AC1 safety cont.240  V
Max. current AC1 safety cont.6  A
Voltage DC1 safety cont.24  V
Max. current DC1 safety cont.6  A
Utilisation cat. AC15/DC13sta.EN 60947-5-1  
Voltage AC15 safety cont.230  V
Max. current AC15 safety cont.3  A
Voltage DC13 safety cont.24  V
Pot. isolation relay outputsYes  

Cascading output as standard output

Number of cascading outputs1  
Galv. isol. casc. aux. S/C ONo  

Serial interface

Number of RS 232 interfaces1  

Environmental data

Ambient temperature standardEN 60068-2-14  
Ambient temperature0 – 60  °C
Storage temperature standardEN 60068-2-1/-2  
Climatic suitability standardEN 60068-2-30  
EN 60068-2-78  
Humidity rating93 % r. h. at 40 °C  
Condensation permitted?Not permitted  
Perm. operating height ASL2000 m  
EMC to standard …EN 61131-2  
Vibration to standard …EN 60068-2-6  
Acc. shock to standard115g  
Overvoltage categoryIII  
Pollution degree clear.&creep.2  
Protection type standardEN 60529  
Protection type, mounting 
Protection type, housing 
Terminal protection type 

Mechanical data

Mounting positionhorizontal on top hat rail  
Connection terminalScrew terminal  
Spring-loaded terminal  
Flex. cond. c/s AWG info24 – 16 AWG  
Cond.flex AWG w/o crimp conn.24 – 12 AWG  
Height dimension94  mm
Width dimension135  mm
Depth dimension121  mm
Net weight499  g
Gross weight519  g
Still not sure what you want?

We are here to help you, send us your details we will assist you to choose right product.

This site is protected by reCAPTCHA and the Google Privacy Policy and Terms of Service apply.
Know the part number Search here

Pilz PNOZ m1p base unit

Fill up the form and we will get back to you in few hours with right details. fill the form to help you better way.