Product characteristics |
---|
Number of inputs and outputs | Number of digital outputs: 2 |
Measuring range | -1…10 bar-14.5…145 psi-0.1…1 MPa |
Process connection | threaded connection G 1/4 internal thread |
Application |
---|
Special feature | Gold-plated contacts |
Measuring element | ceramic-capacitive pressure measuring cell |
Application | for industrial applications |
Media | liquids and gases |
Medium temperature [°C] | -25…80 |
Min. bursting pressure | 150 bar2175 psi15 MPa |
Pressure rating | 75 bar1087 psi7.5 Mpa |
Vacuum resistance [mbar] | -1000 |
Type of pressure | relative pressure; vacuum |
Electrical data |
---|
Operating voltage [V] | 18…30 DC; (to SELV/PELV) |
Current consumption [mA] | < 35 |
Min. insulation resistance [MΩ] | 100; (500 V DC) |
Protection class | III |
Reverse polarity protection | yes |
Power-on delay time [s] | < 0.3 |
Integrated watchdog | yes |
Inputs / outputs |
---|
Number of inputs and outputs | Number of digital outputs: 2 |
Outputs |
---|
Total number of outputs | 2 |
Output signal | switching signal; IO-Link; (configurable) |
Electrical design | PNP/NPN |
Number of digital outputs | 2 |
Output function | normally open / normally closed; (parameterisable) |
Max. voltage drop switching output DC [V] | 2.5 |
Permanent current rating of switching output DC [mA] | 150; (200 (…60 °C) 250 (…40 °C)) |
Switching frequency DC [Hz] | < 170 |
Short-circuit protection | yes |
Type of short-circuit protection | pulsed |
Overload protection | yes |
Measuring/setting range |
---|
Measuring range | -1…10 bar-14.5…145 psi-0.1…1 MPa |
Factory setting / CMPT = 2 |
---|
Set point SP | -0.9…10 bar-13.5…145 psi-0.09…1 MPa |
Reset point rP | -0.95…9.95 bar-14…144.5 psi-0.095…0.995 MPa |
Min. difference between SP and rP | 0.05 bar1 psi0.005 MPa |
In steps of | 0.05 bar0.5 psi0.005 MPa |
Status_B High Resolution / CMPT = 3 |
---|
Set point SP | -0.92…10 bar-13.3…145 psi-0.092…1 MPa |
Reset point rP | -0.97…9.95 bar-14…144.3 psi-0.097…0.995 MPa |
Min. difference between SP and rP | 0.05 bar0.8 psi0.005 MPa |
In steps of | 0.01 bar0.1 psi0.001 MPa |
Accuracy / deviations |
---|
Switch point accuracy [% of the span] | < ± 0,5 |
Repeatability [% of the span] | < ± 0,1; (with temperature fluctuations < 10 K) |
Characteristics deviation [% of the span] | < ± 0,25 (BFSL) / < ± 0,5 (LS); (BFSL = Best Fit Straight Line; LS = limit value setting) |
Hysteresis deviation [% of the span] | < ± 0,25 |
Long-term stability [% of the span] | < ± 0,05; (per 6 months) |
Temperature coefficient zero point [% of the span / 10 K] | < ± 0,2; (0…80 °C) |
Temperature coefficient span [% of the span / 10 K] | < ± 0,2; (0…80 °C) |
Response times |
---|
Response time [ms] | < 3 |
Delay time programmable dS, dr [s] | 0…50 |
Software / programming |
---|
Parameter setting options | hysteresis / window; normally open / normally closed; switching logic; switch-on/switch-off delay; Damping; Display unit |
Interfaces |
---|
Communication interface | IO-Link |
Transmission type | COM2 (38,4 kBaud) |
IO-Link revision | 1.1 |
SDCI standard | IEC 61131-9 |
SIO mode | yes |
Required master port type | A; (when pin 2 not connected: B) |
Supported DeviceIDs | Type of operationDeviceIDFactory setting / CMPT = 2403Status_B High Resolution / CMPT = 3601PN7004311 |
Note | For further information please see the IODD PDF file under “Downloads” |
Factory setting / CMPT = 2 |
---|
Profiles | Smart Sensor: Process Data Variable; Device Identification, Device Diagnosis |
Min. process cycle time [ms] | 2.3 |
IO-Link resolution pressure [bar] | 0.01 |
IO-Link resolution pressure [MPa] | 0.001 |
IO-Link process data (cyclical) | functionbit lengthpressure14binary switching information2 |
IO-Link functions (acyclical) | application specific tag |
Status_B High Resolution / CMPT = 3 |
---|
Profiles | Smart Sensor ED2: Digital Measuring Sensor (0x000A), Identification and Diagnosis (0x4000) |
Min. process cycle time [ms] | 3 |
IO-Link resolution pressure [bar] | 0.005 |
IO-Link resolution pressure [MPa] | 0.0005 |
IO-Link process data (cyclical) | functionbit lengthpressure16device status4binary switching information2 |
IO-Link functions (acyclical) | application specific tag |
Operating conditions |
---|
Ambient temperature [°C] | -25…80 |
Storage temperature [°C] | -40…100 |
Protection | IP 65; IP 67 |
Tests / approvals |
---|
EMC | DIN EN 61000-6-2DIN EN 61000-6-3 |
Shock resistance | DIN EN 60068-2-2750 g (11 ms) |
Vibration resistance | DIN EN 60068-2-620 g (10…2000 Hz) |
MTTF [years] | 260 |
UL approval | UL Approval no.J001 |
Pressure Equipment Directive | Sound engineering practice; can be used for group 2 fluids; group 1 fluids on request |
Mechanical data |
---|
Weight [g] | 241.7 |
Materials | stainless steel (1.4404 / 316L); PBT+PC-GF30; PBT-GF20; PC |
Materials (wetted parts) | stainless steel (1.4404 / 316L); ceramics; FKM |
Min. pressure cycles | 100 million |
Tightening torque [Nm] | 25…35; (recommended tightening torque; depends on lubrication, seal and pressure rating) |
Process connection | threaded connection G 1/4 internal thread |
Displays / operating elements |
---|
Display | Display unit3 x LED, green (bar, psi, MPa)switching status2 x LED, yellowmeasured valuesalphanumeric display, red/green 4-digit |
Remarks |
---|
Pack quantity | 1 pcs. |
Electrical connection |
---|
Connection | Connector: 1 x M12; coding: A; Contacts: gold-plated |