Article No. SMR11GGXFRKG/US-100
Magnetic-inductive flow meter
- Precise measurement of flow, consumption and medium temperature
- High accuracy, repeatability and measurement dynamics
- With switching output, analogue output and pulse output
- Clearly visible 4-digit LED display
Product characteristics
Number of inputs and outputs | Number of digital outputs: 2; Number of analogue outputs: 1 |
---|---|
Measuring range | 0.2…100 l/min0.01…6 m┬│/h |
Process connection | threaded connection G 1 DN25 flat seal |
Application
Special feature | Gold-plated contacts |
---|---|
Application | totaliser function; for industrial applications |
Installation | connection to pipe by means of an adapter |
Media | conductive liquids; water; hydrous media |
Note on media | conductivity: тЙе 20 ┬╡S/cmviscosity: < 70 mm┬▓/s (40 ┬░C) |
Medium temperature [┬░C] | -10…70 |
Pressure rating [bar] | 16 |
Pressure rating [Mpa] | 1.6 |
MAWP (for applications according to CRN) [bar] | 11.2 |
Electrical data
Operating voltage [V] | 18…30 DC; (to SELV/PELV) |
---|---|
Current consumption [mA] | 95; (24 V) |
Protection class | III |
Reverse polarity protection | yes |
Power-on delay time [s] | 5 |
Inputs / outputs
Number of inputs and outputs | Number of digital outputs: 2; Number of analogue outputs: 1 |
---|
Inputs
Inputs | counter reset |
---|
Outputs
Total number of outputs | 2 |
---|---|
Output signal | switching signal; analogue signal; pulse signal; IO-Link; (configurable) |
Electrical design | PNP/NPN |
Number of digital outputs | 2 |
Output function | normally open / normally closed; (parameterisable) |
Max. voltage drop switching output DC [V] | 2 |
Permanent current rating of switching output DC [mA] | 200 |
Number of analogue outputs | 1 |
Analogue current output [mA] | 4…20; (scalable) |
Max. load [╬й] | 500 |
Analogue voltage output [V] | 0…10; (scalable) |
Min. load resistance [╬й] | 2000 |
Pulse output | flow rate meter |
Short-circuit protection | yes |
Type of short-circuit protection | pulsed |
Overload protection | yes |
Measuring/setting range
Measuring range | 0.2…100 l/min0.01…6 m┬│/h |
---|---|
Display range | -120…120 l/min-7.2…7.2 m┬│/h |
Resolution | 0.1 l/min0.005 m┬│/h |
Set point SP | 0.7…100 l/min0.04…6 m┬│/h |
Reset point rP | 0.2…99.5 l/min0.01…5.97 m┬│/h |
Analogue start point ASP | 0…80 l/min0…4.8 m┬│/h |
Analogue end point AEP | 20…100 l/min1.2…6 m┬│/h |
In steps of | 0.1 l/min0.005 m┬│/h |
Volumetric flow quantity monitoring
Pulse value | 0.00001…100 000 m┬│ |
---|---|
Pulse length [s] | 0,0025…2 |
Temperature monitoring
Measuring range [┬░C] | -20…80 |
---|---|
Resolution [┬░C] | 0.2 |
Set point SP [┬░C] | -19.2…80 |
Reset point rP [┬░C] | -19.6…79.6 |
Analogue start point [┬░C] | -20…60 |
Analogue end point [┬░C] | 0…80 |
In steps of [┬░C] | 0.2 |
Accuracy / deviations
Flow monitoring
Accuracy (in the measuring range) | ┬▒ (0,8 % MW + 0,5 % MEW) |
---|---|
Repeatability | ┬▒ 0,2% MEW |
Temperature monitoring
Accuracy [K] | ┬▒ 2,5 (Q > 5 l/min) |
---|
Response times
Flow monitoring
Response time [s] | 0.15; (dAP = 0, T19) |
---|---|
Delay time programmable dS, dr [s] | 0…50 |
Damping process value dAP [s] | 0…5 |
Temperature monitoring
Dynamic response T05 / T09 [s] | T09 = 20 (Q > 5 l/min) |
---|
Software / programming
Parameter setting options | Flow monitoring; quantity meter; Preset counter; Temperature monitoring; hysteresis / window; normally open / normally closed; switching logic; current/voltage/pulse output; start-up delay; display can be deactivated; Display unit |
---|
Interfaces
Communication interface | IO-Link |
---|---|
Transmission type | COM2 (38,4 kBaud) |
IO-Link revision | 1.1 |
SDCI standard | IEC 61131-9 |
Profiles | Smart Sensor: Process Data Variable; Device Identification, Device Diagnosis |
SIO mode | yes |
Required master port type | A |
Process data analogue | 3 |
Process data binary | 2 |
Min. process cycle time [ms] | 5 |
Supported DeviceIDs | Type of operationDeviceIDDefault575 |
Operating conditions
Ambient temperature [┬░C] | -10…60 |
---|---|
Storage temperature [┬░C] | -25…80 |
Protection | IP 67 |
Tests / approvals
EMC | DIN EN 60947-5-9 |
---|---|
CPA approval | model number002MIaccuracy class-maximum allowable error┬▒ 1,5 % FSQ (min)0,01 m┬│/hQ (t)-Q (max)6 m┬│/h |
Shock resistance | DIN IEC 68-2-2720 g (11 ms) |
Vibration resistance | DIN IEC 68-2-65 g (10…2000 Hz) |
MTTF [years] | 145 |
Pressure Equipment Directive | Sound engineering practice; can be used for group 2 fluids; group 1 fluids on request |
Mechanical data
Weight [g] | 577 |
---|---|
Materials | stainless steel (1.4404 / 316L); PBT-GF20; PC; FKM; TPE |
Materials (wetted parts) | stainless steel (1.4404 / 316L); PEEK; FKM |
Process connection | threaded connection G 1 DN25 flat seal |
Displays / operating elements
Display | Display unit6 x LED, green (l/min, m┬│/h, l, m┬│, 10┬│, ┬░C)switching status2 x LED, yellowmeasured valuesalphanumeric display, 4-digitprogrammingalphanumeric display, 4-digit |
---|
Remarks
Remarks | MW = measured valueMEW = Final value of the measuring range |
---|---|
Pack quantity | 1 pcs. |
Electrical connection
Connection | Connector: 1 x M12; coding: A; Contacts: gold-plated |
---|