Article No. CX1500-M310
The CX1500-M310 PROFIBUS fieldbus master enables the distributed collection of process data and signals, even for distant machines or equipment. The use of fieldbus master modules in a CX10x0 system enables the utilization of all Beckhoff fieldbus components (e.g. Bus Couplers, Bus Terminal Controllers, Drive Technology) as distributed control components for the assembly of complex systems. Parallel operation of several identical or different master connections is also possible, e.g. two PROFIBUS masters or one PROFIBUS master and one CANopen master can exist simultaneously within the same system.
Technical data | CX1500-M310 |
---|---|
Fieldbus | PROFIBUS DP, DP-V1, DP-V2 (MC) |
Data transfer rates | 9.6 kbaud…12 Mbaud |
Bus interface | 1 x D-sub socket, 9-pin |
Bus device | max. 125 slaves with up to 244 bytes input, output, parameter, configuration or diagnostic data per slave |
Interface to the CPU | ISA plug and play, 2 kbyte DPRAM |
Max. power loss | 1.8 W |
Properties | PROFIBUS – different DP cycle times are possible for each slave. The error management for each user is freely configurable. |
Dimensions (W x H x D) | 38 mm x 100 mm x 91 mm |
Weight | approx. 190 g |
Operating/storage temperature | 0…+55 °C/-25…+85 °C |
Relative humidity | 95 %, no condensation |
Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27 |
EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 |
Driver | only compatible with TwinCAT 2 |
Protection class | IP 20 |
Approvals/markings | CE, UL |