Article No. KL3204
KL3204 | Bus Terminal, 4-channel analog input, temperature, RTD (Pt100), 16 bit
The KL3204 analog input terminal allows resistance sensors to be connected directly. The Bus Terminal’s circuitry can operate the sensors using 2-wire connection techniques. Linearisation over the full temperature range is realised with the aid of a microprocessor. The temperature range can be selected freely. The Bus Terminals standard settings are: resolution 0.1 °C in the temperature range of Pt100 sensors. The error LEDs indicate sensor faults (e.g. a broken wire). The KL3204 version combines four channels in one housing.
Technical data | KL3204, KS3204 |
---|---|
Number of inputs | 4 |
Power supply | via the K-bus |
Technology | 2-wire |
Sensor types | Pt100, Pt200, Pt500, Pt1000, Ni100, Ni120, Ni1000 resistance measurement (e.g. potentiometer, 10 Ω…1.2/5 kΩ) |
Connection method | 2-wire |
Measuring range | -200…+850 °C (Pt sensors); -60…+250 °C (Ni sensors) |
Resolution | 0.1 °C per digit |
Conversion time | ~ 250 ms |
Measuring current | typ. 0.5 mA |
Measuring error | < ±1 °C |
Electrical isolation | 500 V (K-bus/signal voltage) |
Current consumption power contacts | – (no power contacts) |
Current consumption K-bus | typ. 60 mA |
Bit width in the process image | input: 4 x 16 bit data (4 x 8 bit control/status optional) |
Configuration | no address setting, configuration via Bus Coupler or controller |
Special features | open-circuit recognition |
Weight | approx. 70 g |
Operating/storage temperature | -25…+60 °C/-40…+85 °C |
Relative humidity | 95 %, no condensation |
Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27 |
EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 |
Protect. class/installation pos. | IP 20/variable |
Pluggable wiring | for all KSxxxx Bus Terminals |
Approvals/markings | CE, UL, ATEX, DNV GL |
Ex marking | II 3 G Ex nA IIC T4 Gc |