Article No. KL4001
KL4001 | Bus Terminal, 1-channel analog output, voltage, 0…10 V, 12 bit, differential
The KL4001 analog output terminal generates signals in the range from 0 to 10 V. The voltage is supplied to the process level with a resolution of 12 bits and is electrically isolated. The output channels of the Bus Terminal have a common ground potential. The KL4001 is particularly suitable for signals with electrically isolated ground potentials. The run LEDs give an indication of the data exchange with the Bus Coupler.
| Technical data | KL4001, KS4001 |
|---|---|
| Number of outputs | 1 |
| Power supply | via the K-bus |
| Signal voltage | 0…10 V |
| Load | > 5 kΩ (short-circuit proof) |
| Output error | < ±0.1 % (relative to end value) |
| Resolution | 12 bit |
| Conversion time | ~ 1.5 ms |
| Electrical isolation | 500 V (K-bus/signal voltage) |
| Current consumption power contacts | – (no power contacts) |
| Current consumption K-bus | typ. 75 mA |
| Bit width in the process image | output: 1 x 16 bit data (1 x 8 bit control/status optional) |
| Configuration | no address or configuration setting |
| Special features | potential-free output |
| Weight | approx. 85 g |
| Operating/storage temperature | -25…+60 °C/-40…+85 °C |
| Relative humidity | 95 %, no condensation |
| Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27 |
| EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 |
| Protect. class/installation pos. | IP 20/variable |
| Pluggable wiring | for all KSxxxx Bus Terminals |
| Approvals/markings | CE, UL, ATEX |
| Ex marking | II 3 G Ex nA IIC T4 Gc |