Article No. KL4032
KL4032 | Bus Terminal, 2-channel analog output, voltage, ±10 V, 12 bit, differential
The KL4032 analog output terminal generates signals in the range from -10 to 10 V. The voltage is supplied to the process level with a resolution of 12 bits and is electrically isolated. The output channels of the Bus Terminal have a common ground potential. The run LEDs give an indication of the data exchange with the Bus Coupler.
| Technical data | KL4032, KS4032 | 
|---|---|
| Technology | single-ended | 
| Number of outputs | 2 | 
| Power supply | via the K-bus | 
| Signal voltage | -10…+10 V | 
| Load | > 5 kΩ (short-circuit proof) | 
| Output error | < ±0.1 % (relative to end value) | 
| Resolution | 12 bit | 
| Conversion time | ~ 1.5 ms | 
| Electrical isolation | 500 V (K-bus/signal voltage) | 
| Current consumption power contacts | – (no power contacts) | 
| Current consumption K-bus | typ. 75 mA | 
| Bit width in the process image | output: 2 x 16 bit data (2 x 8 bit control/status optional) | 
| Configuration | no address or configuration setting | 
| Weight | approx. 85 g | 
| Operating/storage temperature | -25…+60 °C/-40…+85 °C | 
| Relative humidity | 95 %, no condensation | 
| Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27 | 
| EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 | 
| Protect. class/installation pos. | IP 20/variable | 
| Pluggable wiring | for all KSxxxx Bus Terminals | 
| Approvals/markings | CE, UL, ATEX, DNV GL | 
| Ex marking | II 3 G Ex nA IIC T4 Gc | 
 
								