ORDER NO. 103489
Order number | 103489 |
Item designation | SOM-4E-0A-C1 |
Gross weight | 0,242kg |
Customs tariff number | 85371098 |
AS-Interface Safety at Work safe output SOM
- 1 redundant OSSD
- Control by SMOx/GMOx
- Control by machine control
- Up to 4 inputs
- Diagnostics via AS-Interface
OSSDs
The OSSD is of redundant design according to category 4 EN ISO 13849-1. Safety-related control is via the bus by a suitable monitor, for example by a GMOx or SMOx. Operational switching is also possible directly by the control system with appropriate parameter settings.
Inputs and outputs
A feedback loop can be connected directly to the SOM. Depending on the parameter settings, further inputs and outputs can also be used.
LED function display
PWR | Green, AS-Interface power |
ASi | Red, bus communication |
OUT | Yellow, state of output signal switching device |
ALARM | Red, can be set as required by control system |
I1…I3 | State of the corresponding input |
1.Y1 | State of the input |
Controls and indicators
LED indicator | |
1 x LED yellow (1. Y1) state EDM input 1.Y1 | |
LED green (Pwr) AS-i power supply | |
LED red (Fault) AS-i fault | |
LED red (Alarm) PLC is signaling alarm | |
LED yellow (Out) relay has switched and error message | |
3 LEDs yellow (I1, I2, I3) state of input E1, E2 and E3 |
Electrical connection ratings
Connecting cable | 9W |
ASI operating current | max. 200 mA |
ASI voltage | 30 V |
Rated insulation voltage Ui | 6000 V |
Utilization category | |
AC-15 | 3A 250V |
DC-13 | 3A 24V |
Current | 0.1 A Supply for sensors |
Overvoltage category according to IEC EN 60664-1 | 3 |
Mechanical values and environment
Connection | Connection terminals |
Degree of protection | IP20 |
Material | |
Housing | Polyamide PA 6.6 |
Reaction time | |
Safety circuit off | max. 50 ms |
Mounting type | Mounting rail 35 mm according to DIN EN 60715 TH35 |
Ambient temperature | 0 … +55 °C |
Reliability values acc. to EN ISO 13849-1
Mission time | 20 y |
Category | 4 |
Performance Level | PL e |
PFHD | 3.3 x 10-9 |
SIL CL | 3 |
Miscellaneous
in compliance with | EN 61 508, EN 62 061, EN ISO 13 849-1 |
Interface, bus
Data interface | Address programming socket AS-i (ADDR) |