| Product characteristics |
|---|
| Electrical design | PNP |
| Output function | normally closed |
| Sensing range [mm] | 10 |
| Housing | threaded type |
| Dimensions [mm] | M30 x 1.5 / L = 92 |
| Electrical data |
|---|
| Operating voltage [V] | 10…36 DC |
| Current consumption [mA] | 15; (24 V) |
| Protection class | II |
| Reverse polarity protection | yes |
| Outputs |
|---|
| Electrical design | PNP |
| Output function | normally closed |
| Max. voltage drop switching output DC [V] | 2.5 |
| Permanent current rating of switching output DC [mA] | 250 |
| Switching frequency DC [Hz] | 250 |
| Short-circuit protection | yes |
| Type of short-circuit protection | pulsed |
| Overload protection | yes |
| Detection zone |
|---|
| Sensing range [mm] | 10 |
| Real sensing range Sr [mm] | 10 ± 10 % |
| Operating distance [mm] | 0…8.1 |
| Accuracy / deviations |
|---|
| Correction factor | steel: 1 / stainless steel: 0.7 / brass: 0.4 / aluminium: 0.3 / copper: 0.2 |
| Hysteresis [% of Sr] | 1…15 |
| Switch point drift [% of Sr] | -10…10 |