Article No. PN-001BRER14-MFRKG/US/ /V
Pressure sensor with display
- Programmable switching output with IO-Link and analogue output
- Red/green display for clear identification of the acceptable range
- The process connection can be rotated for optimum alignment
- With long-term stability thanks to high overload protection
- Robust design for use in harsh industrial environments
Product characteristics
Number of inputs and outputs | Number of digital outputs: 1; Number of analogue outputs: 1 |
---|---|
Measuring range | 0…1 bar0…1000 mbar0…14.5 psi0…29.5 inHg0…100 kPa |
Process connection | threaded connection G 1/4 internal thread M6 I |
Application
Special feature | Gold-plated contacts |
---|---|
Measuring element | ceramic-capacitive pressure measuring cell |
Application | for industrial applications |
Media | liquids and gases |
Medium temperature [°C] | -25…80 |
Min. bursting pressure | 30000 mbar450 psi880 inHg3000 kPa |
Pressure rating | 10000 mbar145 psi290 inHg1000 kPa |
Vacuum resistance [mbar] | -1000 |
Type of pressure | relative pressure |
Electrical data
Operating voltage [V] | 18…30 DC; (to SELV/PELV) |
---|---|
Current consumption [mA] | < 35 |
Min. insulation resistance [MΩ] | 100; (500 V DC) |
Protection class | III |
Reverse polarity protection | yes |
Power-on delay time [s] | 0.3 |
Integrated watchdog | yes |
Inputs / outputs
Number of inputs and outputs | Number of digital outputs: 1; Number of analogue outputs: 1 |
---|
Outputs
Total number of outputs | 2 |
---|---|
Output signal | switching signal; analogue signal; IO-Link; (configurable) |
Electrical design | PNP |
Number of digital outputs | 1 |
Output function | normally open / normally closed; (parameterisable) |
Max. voltage drop switching output DC [V] | 2.5 |
Permanent current rating of switching output DC [mA] | 150; (200 (…60 °C) 250 (…40 °C)) |
Switching frequency DC [Hz] | < 170 |
Number of analogue outputs | 1 |
Analogue current output [mA] | 4…20 |
Max. load [Ω] | 500 |
Analogue voltage output [V] | 0…10 |
Min. load resistance [Ω] | 2000 |
Short-circuit protection | yes |
Type of short-circuit protection | pulsed |
Overload protection | yes |
Measuring/setting range
Measuring range | 0…1 bar0…1000 mbar0…14.5 psi0…29.5 inHg0…100 kPa |
---|
Factory setting / CMPT = 2
Set point SP | 10…1000 mbar0.1…14.5 psi0.2…29.5 inHg1…100 kPa |
---|---|
Reset point rP | 5…995 mbar0.05…14.45 psi0.1…29.4 inHg0.5…99.5 kPa |
Min. difference between SP and rP | 5 mbar0.1 psi0.2 inHg0.5 kPa |
In steps of | 5 mbar0.05 psi0.1 inHg0.5 kPa |
Status_B High Resolution / CMPT = 3
Set point SP | 8…1000 mbar0.12…14.5 psi0.2…29.5 inHg0.8…100 kPa |
---|---|
Reset point rP | 3…995 mbar0.05…14.43 psi0.1…29.4 inHg0.3…99.5 kPa |
Min. difference between SP and rP | 5 mbar0.08 psi0.2 inHg0.5 kPa |
In steps of | 1 mbar0.01 psi0.1 inHg0.1 kPa |
Accuracy / deviations
Switch point accuracy [% of the span] | < ± 0,5 |
---|---|
Repeatability [% of the span] | < ± 0,1; (with temperature fluctuations < 10 K) |
Characteristics deviation [% of the span] | < ± 0,25 (BFSL) / < ± 0,5 (LS); (BFSL = Best Fit Straight Line; LS = limit value setting) |
Hysteresis deviation [% of the span] | < ± 0,25 |
Long-term stability [% of the span] | < ± 0,05; (per 6 months) |
Temperature coefficient zero point [% of the span / 10 K] | < ± 0,2; (-0…80 °C) |
Temperature coefficient span [% of the span / 10 K] | < ± 0,2; (-0…80 °C) |
Response times
Response time [ms] | < 3 |
---|---|
Delay time programmable dS, dr [s] | 0…50 |
Damping process value dAP [s] | 0…4 |
Damping for the analogue output dAA [s] | 0…4 |
Max. response time analogue output [ms] | 3 |
Software / programming
Parameter setting options | hysteresis / window; normally open / normally closed; switch-on/switch-off delay; Damping; Display unit; current/voltage output |
---|
Interfaces
Communication interface | IO-Link |
---|---|
Transmission type | COM2 (38,4 kBaud) |
IO-Link revision | 1.1 |
SDCI standard | IEC 61131-9 |
SIO mode | yes |
Required master port type | A |
Process data analogue | 1 |
Process data binary | 1 |
Supported DeviceIDs | Type of operationDeviceIDFactory setting / CMPT = 2433Status_B High Resolution / CMPT = 3618 |
Note | For further information please see the IODD PDF file under “Downloads” |
Factory setting / CMPT = 2
Profiles | Smart Sensor: Process Data Variable; Device Identification, Device Diagnosis |
---|---|
Min. process cycle time [ms] | 2.3 |
IO-Link resolution pressure [mbar] | 1 |
IO-Link resolution pressure [MPa] | 0.0001 |
IO-Link process data (cyclical) | functionbit lengthpressure14binary switching information1 |
IO-Link functions (acyclical) | application specific tag |
Status_B High Resolution / CMPT = 3
Profiles | Smart Sensor ED2: Digital Measuring Sensor (0x000A), Identification and Diagnosis (0x4000) |
---|---|
Min. process cycle time [ms] | 3 |
IO-Link resolution pressure [mbar] | 0.5 |
IO-Link resolution pressure [MPa] | 0.00005 |
IO-Link process data (cyclical) | functionbit lengthpressure16device status4binary switching information1 |
IO-Link functions (acyclical) | application specific tag |
Operating conditions
Ambient temperature [°C] | -25…80 |
---|---|
Storage temperature [°C] | -40…100 |
Protection | IP 65; IP 67 |
Tests / approvals
EMC | DIN EN 61000-6-2DIN EN 61000-6-3 |
---|---|
Shock resistance | DIN EN 60068-2-2750 g (11 ms) |
Vibration resistance | DIN EN 60068-2-620 g (10…2000 Hz) |
MTTF [years] | 226 |
UL approval | UL Approval no.J004 |
Pressure Equipment Directive | Sound engineering practice; can be used for group 2 fluids; group 1 fluids on request |
Mechanical data
Weight [g] | 233.5 |
---|---|
Materials | stainless steel (1.4404 / 316L); PBT+PC-GF30; PBT-GF20; PC |
Materials (wetted parts) | stainless steel (1.4404 / 316L); Al2O3 (ceramics); FKM |
Min. pressure cycles | 100 million |
Tightening torque [Nm] | 25…35; (recommended tightening torque; depends on lubrication, seal and pressure rating) |
Process connection | threaded connection G 1/4 internal thread M6 I |
Restrictor element integrated | no (can be retrofitted) |
Displays / operating elements
Display | Display unit4 x LED, green (bar, psi, kPa, inHg)switching status1 x LED, yellowmeasured valuesalphanumeric display, red/green 4-digit |
---|
Remarks
Pack quantity | 1 pcs. |
---|
Electrical connection
Connection | Connector: 1 x M12; coding: A; Contacts: gold-plated |
---|