IFM SH0500 Connecting cable with socket
Sockets are generally used in automation technology to connect sensors and actuators with connectors to splitter boxes.
- Reliable monitoring of liquids and gases in pipes
- Variable process connection using adapters
- Easy setting of the switch points for quick set-up
- Robust stainless steel housing for use in harsh industrial environments
- LED bar graph for indication of switch point and flow
Product characteristics | |
---|---|
Number of inputs and outputs | Number of digital outputs: 1 |
Process connection | M18 x 1,5 internal thread |
Application | |
Media | Liquids; Gases |
Medium temperature [°C] | -25…80 |
Pressure rating [bar] | 30 |
Liquids | |
Medium temperature [°C] | -25…80 |
Gases | |
Medium temperature [°C] | -25…80 |
Electrical data | |
Operating voltage [V] | 19…36 DC |
Current consumption [mA] | < 60 |
Protection class | III |
Reverse polarity protection | yes |
Power-on delay time [s] | 10 |
Inputs / outputs | |
Number of inputs and outputs | Number of digital outputs: 1 |
Outputs | |
Total number of outputs | 1 |
Output signal | switching signal |
Electrical design | PNP |
Number of digital outputs | 1 |
Output function | normally open / normally closed; (parameterisable) |
Max. voltage drop switching output DC [V] | 2.5 |
Permanent current rating of switching output DC [mA] | 250 |
Short-circuit protection | yes |
Type of short-circuit protection | pulsed |
Overload protection | yes |
Measuring/setting range | |
Probe length L [mm] | 45 |
Liquids | |
Setting range [cm/s] | 3…300 |
Greatest sensitivity [cm/s] | 3…100 |
Gases | |
Setting range [cm/s] | 200…3000 |
Greatest sensitivity [cm/s] | 200…800 |
Accuracy / deviations | |
Repeatability [cm/s] | 1…5 |
Note on repeatability | for water 5…100 cm/s; 25 °CFactory setting |
Temperature drift [cm/s x 1/K] | 0.1; (for water 5…100 cm/s; 10…70 °C) |
Temperature gradient [K/min] | 300 |
Switch point accuracy [cm/s] | ± 2…± 10; (for water 5…100 cm/s; 25 °C; Factory setting) |
Hysteresis [cm/s] | 2…5; (for water 5…100 cm/s; 25 °C; Factory setting) |
Response times | |
Response time [s] | 1…10 |
Liquids | |
Response time [s] | 1…10 |
Gases | |
Response time [s] | 1…10 |
Software / programming | |
Adjustment of the switch point | pushbutton |
Operating conditions | |
Ambient temperature [°C] | -25…80 |
Storage temperature [°C] | -25…100 |
Protection | IP 67 |
Tests / approvals | |
EMC | EN 61000-4-2 ESD4 kV CD / 8 kV ADEN 61000-4-3 HF radiated10 V/mEN 61000-4-4 Burst2 kVEN 61000-4-6 HF conducted10 V |
Shock resistance | DIN IEC 68-2-2750 g (11 ms) |
Vibration resistance | DIN EN 60068-2-620 g (55…2000 Hz) |
MTTF [years] | 298 |
Mechanical data | |
Weight [g] | 246 |
Dimensions [mm] | M18 x 1.5 |
Thread designation | M18 x 1.5 |
Materials | stainless steel (1.4404 / 316L); stainless steel (1.4310 / 301); PC; PBT-GF20; EPDM/X |
Materials (wetted parts) | stainless steel (1.4404 / 316L); O-ring: FKM 80 Shore A |
Process connection | M18 x 1,5 internal thread |
Displays / operating elements | |
Display | function10 x LED, three-colour |
Remarks | |
Pack quantity | 1 pcs. |
Electrical connection | |
Connection | Connector: 1 x M12 |
ifm electronic gmbh • Friedrichstraße 1 • 45128 Essen — We reserve the right to make technical alterations without prior notice. — EN-GB — SI5000-01 — 09.07.2013 |