Article No. TA-025CLER14-A-ZVG/US
Temperature transmitter
- High precision across the entire temperature measurement range
- Particularly good response dynamics and very short power-on delay time
- Robust stainless steel housing with very high pressure rating
- Precise analogue output and user-friendly communication via IO-Link
- High protection rating for the requirements of harsh industrial environments
Product characteristics
| Number of inputs and outputs | Number of analogue outputs: 1 |
|---|---|
| Measuring range [°C] | -50…150 |
| Process connection | threaded connection G 1/4 |
| Installation length EL [mm] | 25 |
Application
| Special feature | Gold-plated contacts |
|---|---|
| Measuring element | 1 x Pt 1000; (to DIN EN 60751, class A) |
| Media | liquids and gases |
| Pressure rating [bar] | 400 |
| Note on pressure rating | sensorWhen mounted in adapters the specifications of the adapter data sheet apply. |
Electrical data
| Operating voltage [V] | 18…32 DC; (“supply class 2” to cULus) |
|---|---|
| Current consumption [mA] | < 50 |
| Protection class | III |
| Reverse polarity protection | yes |
| Power-on delay time [s] | 1 |
Inputs / outputs
| Number of inputs and outputs | Number of analogue outputs: 1 |
|---|
Outputs
| Total number of outputs | 1 |
|---|---|
| Output signal | analogue signal; IO-Link; (configurable) |
| Number of analogue outputs | 1 |
| Analogue current output [mA] | 4…20 |
| Max. load [Ω] | 250; ((18…19 V); 19…32 V: 300 Ω) |
| Short-circuit protection | yes |
| Overload protection | yes |
Measuring/setting range
| Measuring range [°C] | -50…150 |
|---|---|
| Factory setting | -50…150 °C |
Resolution
| Resolution of analogue output [K] | 0.04 |
|---|
Accuracy / deviations
| Precision analogue output [K] | ± 0,3 + (± 0,1 % MS) |
|---|---|
| Temperature coefficient [% of the span / 10 K] | 0,1; (in case of deviation from the reference condition 25 ± 5 °C) |
Response times
| Dynamic response T05 / T09 [s] | 1 / 3 |
|---|
Interfaces
| Communication interface | IO-Link |
|---|---|
| Transmission type | COM2 (38,4 kBaud) |
| IO-Link revision | 1.1 |
Operating conditions
| Ambient temperature [°C] | -25…80 |
|---|---|
| Storage temperature [°C] | -40…100 |
| Protection | IP 67; IP 68; IP 69K |
Tests / approvals
| EMC | DIN EN 61000-6-2 |
|---|---|
| Shock resistance | DIN IEC 68-2-2750 g (11 ms) |
| Vibration resistance | DIN IEC 68-2-620 g (10…2000 Hz) |
| MTTF [years] | 572 |
| UL approval | UL Approval no.K002 |
Mechanical data
| Weight [g] | 84 |
|---|---|
| Dimensions [mm] | Ø 18.7 |
| Materials | stainless steel (1.4404 / 316L); PEI; FKM |
| Materials (wetted parts) | stainless steel (1.4404 / 316L); O-ring: FKM |
| Tightening torque [Nm] | 35 |
| Process connection | threaded connection G 1/4 |
| Probe diameter [mm] | 6 |
| Installation length EL [mm] | 25 |
Displays / operating elements
| Display | operating status1 x LED, green |
|---|
Remarks
| Remarks | MS = set measuring span |
|---|---|
| Pack quantity | 1 pcs. |
Electrical connection
| Connection | Connector: 1 x M12; coding: A; Contacts: gold-plated |
|---|